Burkert Type 8630 Manuel d'utilisateur Page 97

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 186
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 96
8630 - 95
OPERATING THE PROCESS CONTROLLER
P.CO - INP
Specification of the signal type for process actual value
Frequency signal (flow rate) 0 ... 1000 Hz
Connection with Pt100 (temperature)
- 20 °C ... + 220 °C
Configuration for flow rate controller - option
standard signal current 4 ... 20 mA (flow rate, pressure,
le
vel)
Setting in 10 steps
P.CO - FILT
Filtering of the process actual value input
FILT XX
Setting in 10 steps: 0 ... 9
Valid for all types of process actual value.
Filter has low-pass behavior (PT1).
Range: 0 ... 9
Factory setting: 0
Setting Corresponds to limiting
frequency (Hz)
Effect
0 10 minimum filtering
15
22
31
40.5
50.2
60.1
70.07
80.05
9 0.03 maximum filtering
Vue de la page 96
1 2 ... 92 93 94 95 96 97 98 99 100 101 102 ... 185 186

Commentaires sur ces manuels

Pas de commentaire