Vue de la page 71
70 - 8630
OPERATION AND CONTROLLER FUNCTIONS
X.LIMIT
Limitation of the mechanical stroke range
Factory setting:
LIM
= 0%,
LIM
= 100%
This supplementary function limits the (physical) stroke to preset % values (minimum and maximum).
The range of the limited stroke is thereby set to 100 %.If the limited stroke range is left during operation,
negative or positive POS values greater than 100 % are displayed.
Entering the start value of the stroke range in %,
0 ... 50 % of the overall stroke
Entering the end value of the stroke rage in %,
50 ... 100 % of the overall stroke
The minimum separation between
LIM
and
LIM
is 50 %.
XXX
XX
Setpoint [mA]
(INP)
limited
stroke
Limited
stroke [%]
(POS)
Physical stroke
[%] (POS)
unlimited
stroke
Control range in
automatic mode
Correcting range in manual mode