Burkert Type 8630 Manuel d'utilisateur Page 65

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 186
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 64
8630 - 63
OPERATION AND CONTROLLER FUNCTIONS
CHARACT
Selection of the transfer characteristic between input signal (position setpoint)
and stroke (correction curve)
Customized characteristic
Factory setting:
CHA LIN
With this function, you can select a transfer characteristic with respect to setpoint position (setpoint
position CMD) and valve stroke (POS) to correct the flow or operating curve.
The flow characteristic k
v
= f(s) describes the flow through a valve, expressed by the k
v
value, as a
function of the stroke s of the actuator spindle. It is determined by the shape of the valve seat and the
seat seal. In general, two types of flow characteristic are realized: the linear and the equipercentile.
With linear characteristics, equal changes in stroke ds are allocated to equal changes in k
v
value dk
v
(dk
V
= n
lin
* ds).
With an equipercentile characteristic, a change in stroke ds corresponds to an equipercentile change in
k
v
value
(dk
V
/k
V
= n
gleichpr
* ds).
The operating characteristic Q = f(s) represents the relationship between the volumetric flow Q passing
through a valve installed in a system and the stroke s. This characteristic contains the properties of the
piping, pumps and consumers. It hence has a different shape from the flow characteristic.
Linear characteristic
Equipercentile characteristic 1:25
Equipercentile characteristic: 1:33
Equipercentile characteristic 1:50
Inverse equipercentile characteristic 25:1
Inverse equipercentile characteristic 33:1
Inverse equipercentile characteristic 50:1
User-defined characteristic, freely
programmable via fixed points
Vue de la page 64
1 2 ... 60 61 62 63 64 65 66 67 68 69 70 ... 185 186

Commentaires sur ces manuels

Pas de commentaire