Burkert Type 8619 Manuel d'utilisateur Page 9

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 40
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 8
7
Technical data
6. TECHNICAL DATA
6.1. Conditions of use
Ambient temperature -10 to +70 °C (operating, without memory card), restricted to 0 ... +70°C if
a memory card is used
Air humidity < 85 %, non condensated
Height above sea level max. 2000 m
Protection rating IP65 and NEMA4X (on front, once built in, housing closed)
IP20 (non front parts inside the housing)
6.2. Compliance to standards and directives
The device conforms to the EC directives through the following standards:
EMC: EN 61000-6-2, EN 61000-6-3
Vibration: EN 60068-2-6
Shock: EN 60068-2-27
UL recognised devices (
) for the United States of America and Canada comply to the following
standards:
UL 61010-1
CAN/CSA-C22.2 n° 61010-1
6.3. General technical data
6.3.1. Mechanical data
Mechanical data Material
Built in and locking system / seal PPO / silicone
Front cover, upper layer, and keys / front
cover, sublayer, and display
Silicone / PC
Rear plate Stainless steel 304
Terminal blocks PBT, contacts in gold-plated copper alloy
Ground screw + spring washer Stainless steel 316 (A4)
Type 8619